TEP108LE-S4E

Trenton Refrigeration TEP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty4 countTEP + TEP-GEN-E p.5
capacity114500 btu_hTEP + TEP-GEN-E p.5
111200 btu_hTEP + TEP-GEN-E p.5
108000 btu_hTEP + TEP-GEN-E p.5
98300 btu_hTEP + TEP-GEN-E p.5
91800 btu_hTEP + TEP-GEN-E p.5
93300 btu_hp.5
90600 btu_hp.5
88000 btu_hp.5
81000 btu_hp.5
74800 btu_hp.5
114500 btu_hTEP + TEP-GEN-E p.5
111200 btu_hTEP + TEP-GEN-E p.5
108000 btu_hTEP + TEP-GEN-E p.5
98300 btu_hTEP + TEP-GEN-E p.5
91800 btu_hTEP + TEP-GEN-E p.5
93300 btu_hp.8
90600 btu_hp.8
88000 btu_hp.8
81000 btu_hp.8
74800 btu_hp.8
airflow13600 cfmTEP + TEP-GEN-E p.5
6420 l_sTEP + TEP-GEN-E p.5
refrigerant charge20.6 lbTEP + TEP-GEN-E p.5
9.3 kgTEP + TEP-GEN-E p.5
19.1 lbp.5
8.7 kgp.5
18.5 lbTEP + TEP-GEN-E p.5
8.4 kgTEP + TEP-GEN-E p.5
19.8 lbTEP + TEP-GEN-E p.5
8.9 kgTEP + TEP-GEN-E p.5
19.1 lbp.8
8.7 kgp.8
awef rating4.15 ratiop.35
4.15 ratiop.35
4.15 ratiop.35
4.15 ratiop.35
4.15 ratiop.35
4.15 ratiop.35
4.15 ratiop.33
suction od2 1/8 inchesTEP + TEP-GEN-E p.37
distributor inlet1 5/8 inchesp.37
1 5/8 inchessources differTEP p.37
1 5/8 inchessources differTEP-GEN-E p.36
1 3/8 inchessources differTEP-GEN-E p.36
side port connection1 1/8 inchesp.37
1 1/8 inchesp.36
hot gas connection1 3/8 inchesp.37
shipping weight575 lbTEP + TEP-GEN-E p.38
261 kgTEP + TEP-GEN-E p.38
mca41.1 ampssources differTEP p.13
21 ampssources differTEP-GEN-E p.13
41.1 ampssources differTEP-GEN-E p.13
esp circuit 460 1 60 mop a45TEP + TEP-GEN-E p.13
voltage460 VTEP + TEP-GEN-E p.?
phase1 phTEP + TEP-GEN-E p.?
frequency60 HzTEP + TEP-GEN-E p.?
r454a erte 5 zp ebste 8 zpOTE-30-ZPp.41
r454c r455a r407a r448a r449a erve 5 zp ebsve 8 zpOVE-30-ZPp.41
r404a r507 ebsse 6 zpOSE-30-ZPp.41
liquid line od15.9 mmp.51
suction line od41.3 mmp.51
maximum line length 3m minimum room area m224p.51
maximum line length 7 6m29p.51
maximum line length 15 2m36p.51
maximum line length 30 5m51**p.51
motor hp1 hpp.13
motor fla10 ampsp.13
motor watts1400 wattsp.13
mop25 ampsp.13
total watts15116 wattsp.13
total amps32.9 ampsp.13
defrost heaters 460 1 60 mop a45p.13
esp circuit mca41.1 ampsp.18

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP_1109296, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP-GEN-E_1112932, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TEP108LE-S4E460/1/60Check availability

Nomenclature

Position / meaningValue
capacity code108
capacity mbh108
defrostE
generation suffixE
temp classL
voltageS4

Parts

11 factory parts for this unit: 11from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleA20--Check availability
Electronic expansion valveE3V55order as E3V55BWRC1--Check availability
Safety check valveCSOV17order as CSOV-17S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB19order as B19S2-7/8--Check availability
TXVEBSSE-13-C--Check availability
TXVOSE-21-ZP--Check availability
TXVOSE-30-ZP--Check availability
TXVOVE-20-C--Check availability
TXVOVE-20-ZPorder as OVE-20-ZP40--Check availability
TXVOVE-30-ZPorder as OVE-30-ZP40--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKEP108LE-S4Eshared catalog stem
BallyBEP108LE-S4Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP108LE-S4E?

TEP108LE-S4E has a rated capacity of 114500 btu_h. See the specifications table for rating conditions.

What voltage does TEP108LE-S4E require?

TEP108LE-S4E runs on 460 V supply power.

Related models in TEP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.