TEP101ME-T4E

Trenton Refrigeration TEP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
capacity101000 btu_hTEP + TEP-GEN-E p.4
100000 btu_hTEP + TEP-GEN-E p.4
99000 btu_hTEP + TEP-GEN-E p.4
82400 btu_hTEP + TEP-GEN-E p.4
81600 btu_hTEP + TEP-GEN-E p.4
80800 btu_hTEP + TEP-GEN-E p.4
101000 btu_hTEP + TEP-GEN-E p.4
100000 btu_hTEP + TEP-GEN-E p.4
99000 btu_hTEP + TEP-GEN-E p.4
airflow10600 cfmTEP + TEP-GEN-E p.4
5000 l_sTEP + TEP-GEN-E p.4
refrigerant charge18.2 lbTEP + TEP-GEN-E p.4
8.3 kgTEP + TEP-GEN-E p.4
17.2 lbTEP + TEP-GEN-E p.4
7.8 kgTEP + TEP-GEN-E p.4
16.4 lbTEP + TEP-GEN-E p.4
7.5 kgTEP + TEP-GEN-E p.4
17.5 lbTEP + TEP-GEN-E p.4
8 kgTEP + TEP-GEN-E p.4
awef rating9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.33
suction od1 5/8 inchesTEP + TEP-GEN-E p.37
distributor inlet1 3/8 inchessources differTEP p.37
1 3/8 inchessources differTEP-GEN-E p.35
1 1/8 inchessources differTEP-GEN-E p.36
1 3/8 inchesp.37
side port connection0.875 inchesp.37
0.875 inchesp.36
hot gas connection1 1/8 inchesp.37
shipping weight485 lbTEP + TEP-GEN-E p.38
220 kgTEP + TEP-GEN-E p.38
mca21.3 ampssources differTEP p.13
21 ampssources differTEP-GEN-E p.14
21.3 ampssources differTEP-GEN-E p.14
esp circuit 460 3 60 mop a25TEP + TEP-GEN-E p.13
voltage460 VTEP + TEP-GEN-E p.?
phase3 phTEP + TEP-GEN-E p.?
frequency60 HzTEP + TEP-GEN-E p.?
fan qty3 countp.35
r454a erte 5 cEBSTE-15-Cp.40
r454c r455a r407a r448a r449a erve 5 cEBSVE-15-Cp.40
r404a r507 erse 3 1 2 c erse 4 cEBSSE-13-Cp.40
liquid line od15.9 mmp.51
suction line od41.3 mmp.51
maximum line length 3m minimum room area m222p.51
maximum line length 7 6m26p.51
maximum line length 15 2m34p.51
maximum line length 30 5m49**p.51
motor hp1 hpp.14
motor fla7.5 ampsp.14
motor watts1050 wattsp.14
mop25 ampsp.14
total watts12940 wattsp.14
total amps17.1 ampsp.14
defrost heaters 460 3 60 mop a25p.14
esp circuit mca21.3 ampsp.18

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP_1109296, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP-GEN-E_1112932, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TEP101ME-T4E460/3/60Check availability

Nomenclature

Position / meaningValue
capacity code101
capacity mbh101
defrostE
generation suffixE
temp classM
voltageT4

Parts

7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleC12--Check availability
Electronic expansion valveE3V55order as E3V55BWRC1--Check availability
Safety check valveCSOV17order as CSOV-17S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB14order as B14S2-5/8ODF--Check availability
TXVEBSSE-13-C--Check availability
TXVEBSVE-15-C--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKEP101ME-T4Eshared catalog stem
BallyBEP101ME-T4Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP101ME-T4E?

TEP101ME-T4E has a rated capacity of 101000 btu_h. See the specifications table for rating conditions.

What voltage does TEP101ME-T4E require?

TEP101ME-T4E runs on 460 V supply power.

Related models in TEP