TEP088ME-T3E

Trenton Refrigeration TEP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty3 countTEP + TEP-GEN-E p.4
capacity87700 btu_hTEP + TEP-GEN-E p.4
86800 btu_hTEP + TEP-GEN-E p.4
85900 btu_hTEP + TEP-GEN-E p.4
71300 btu_hTEP + TEP-GEN-E p.4
70600 btu_hTEP + TEP-GEN-E p.4
69900 btu_hTEP + TEP-GEN-E p.4
87700 btu_hTEP + TEP-GEN-E p.4
86800 btu_hTEP + TEP-GEN-E p.4
85900 btu_hTEP + TEP-GEN-E p.4
airflow11200 cfmTEP + TEP-GEN-E p.4
5290 l_sTEP + TEP-GEN-E p.4
refrigerant charge13.9 lbTEP + TEP-GEN-E p.4
6.3 kgTEP + TEP-GEN-E p.4
13.1 lbTEP + TEP-GEN-E p.4
6 kgTEP + TEP-GEN-E p.4
12.6 lbTEP + TEP-GEN-E p.4
5.7 kgTEP + TEP-GEN-E p.4
13.3 lbTEP + TEP-GEN-E p.4
6 kgTEP + TEP-GEN-E p.4
awef rating9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.33
suction od1 5/8 inchesTEP + TEP-GEN-E p.37
distributor inlet1 1/8 inchessources differTEP p.37
1 1/8 inchessources differTEP-GEN-E p.35
1 3/8 inchessources differTEP-GEN-E p.36
1 3/8 inchesp.37
side port connection0.875 inchesp.37
0.875 inchesp.36
hot gas connection1 1/8 inchesp.37
shipping weight455 lbTEP + TEP-GEN-E p.38
207 kgTEP + TEP-GEN-E p.38
mca42.7 ampssources differTEP p.12
16 ampssources differTEP-GEN-E p.12
42.8 ampssources differTEP-GEN-E p.12
esp circuit 208 230 3 60 mop a45TEP + TEP-GEN-E p.12
voltage208 VTEP + TEP-GEN-E p.?
phase3 phTEP + TEP-GEN-E p.?
frequency60 HzTEP + TEP-GEN-E p.?
r454a erte 5 cEBSTE-15-Cp.40
r454c r455a r407a r448a r449a erve 5 cEBSVE-15-Cp.40
r404a r507 erse 3 1 2 c erse 4 cEBSSE-13-Cp.40
liquid line od15.9 mmp.51
suction line od41.3 mmp.51
maximum line length 3m minimum room area m217p.51
maximum line length 7 6m22p.51
maximum line length 15 2m30p.51
maximum line length 30 5m45p.51
motor hp0.5 hpp.12
motor fla12.6 ampsp.12
motor watts1050 wattsp.12
mop20 ampsp.12
total watts12940 wattsp.12
total amps34.2 ampsp.12
defrost heaters 208 230 3 60 mop a45p.12
esp circuit mca42.7 ampsp.17

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP_1109296, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP-GEN-E_1112932, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TEP088ME-T3E208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code088
capacity mbh88
defrostE
generation suffixE
temp classM
voltageT3

Parts

7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleE10--Check availability
Electronic expansion valveE3V55order as E3V55BWRC1--Check availability
Safety check valveCSOV17order as CSOV-17S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB14order as B14S2-5/8ODF--Check availability
TXVEBSSE-13-C--Check availability
TXVEBSVE-15-C--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKEP088ME-T3Eshared catalog stem
BallyBEP088ME-T3Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP088ME-T3E?

TEP088ME-T3E has a rated capacity of 87700 btu_h. See the specifications table for rating conditions.

What voltage does TEP088ME-T3E require?

TEP088ME-T3E runs on 208 V supply power.

Related models in TEP