TEP077FR-S2D

Trenton Refrigeration TEP extended profile evaporators- a2l for "e" generation evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty3 countp.42
capacity66000 btu_hp.42
64200 btu_hp.42
62300 btu_hp.42
57300 btu_hp.42
53000 btu_hp.42
airflow10300 cfmp.42
4860 l_sp.42
refrigerant charge16.9 lbp.42
7.7 kgp.42
awef rating4.15 ratiop.47
suction od0.875 inchesp.49
distributor inlet0.875 inchesp.49
side port connection0.5 inchesp.49
hot gas connection0.625 inchessources differTEP p.49
216 inchessources differTEP p.50
475 lbp.50
nozle hgG2-1/2p.50
with electric heater pan model tep077FGp.50
shipping weight450 lbp.50
204 kgp.50
motor hp0.5 hpp.43
motor fla12.6 ampsp.43
total watts1050 wattsp.43
mca15 ampsp.43
mop20 ampsp.43
voltage208 Vp.?
phase1 php.?
frequency60 Hzp.?

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP_1109296, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TEP077FR-S2D208-230/1/60Check availability

Nomenclature

Position / meaningValue
capacity code077
capacity mbh77
defrostR
generation suffixD
temp classF
voltageS2

Parts

1 factory parts for this unit: 1from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

PartPart numberQtyListAvailability
Distributor nozzleG2-1/2--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKEP077FR-S2Dshared catalog stem
BallyBEP077FR-S2Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP077FR-S2D?

TEP077FR-S2D has a rated capacity of 66000 btu_h. See the specifications table for rating conditions.

What voltage does TEP077FR-S2D require?

TEP077FR-S2D runs on 208 V supply power.

Related models in TEP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.