Trenton Refrigeration · TEP · Extended Profile Evaporators- A2L For "E" Generation

TEP077FE-T4D

Trenton Refrigeration TEP extended profile s- a2l for "e" generation evaporator.

35 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
fan qty3 countp.42
3 countp.45
capacity66000 btu_hp.42
64200 btu_hp.42
62300 btu_hp.42
57300 btu_hp.42
53000 btu_hp.42
airflow10300 cfmp.42
4860 l_sp.42
refrigerant charge16.9 lbp.42
7.7 kgp.42
awef rating4.15 ratiop.47
suction od0.875 inchesp.49
0.875 inchesp.49
distributor inlet0.875 inchesp.49
0.875 inchesp.49
reverse cycle 3 pipe defrost side port connection od sweat0.5p.49
hot gas connection0.625 inchesp.49
distributor nozzleG2-1/2 part_idp.50
nozle hgG2-1/2p.50
liquid line od sweat0.5p.49
shipping weight470 lbp.50
213 kgp.50
motor hp1 hpp.45
motor fla7.5 ampsp.45
total watts1050 wattsp.45
12940 wattsp.45
mca15 ampsp.45
21.3 ampsp.45
fan motors standard ec motors mop a20p.45
total amps17.1 ampsp.45
defrost heaters 460 3 60 mop a25p.45
voltage460 Vp.?
phase3 php.?
frequency60 Hzp.?

Sources: TEP_1109296 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
TEP077FE-T4D460/3/60Check availability

Nomenclature

Position / meaningValue
capacity code77
defrostE
fan count0
generation suffixD
temp classF
voltageT4

Cross references

BrandEquivalent modelBasis
KeepRiteKEP077FE-T4Dshared catalog stem
BallyBEP077FE-T4Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP077FE-T4D?

TEP077FE-T4D has a rated capacity of 66000 btu_h. See the specifications table for rating conditions.

What voltage does TEP077FE-T4D require?

TEP077FE-T4D runs on 460 V supply power.

Related models in TEP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.