Trenton Refrigeration · TEP · Extended Profile Evaporators- A2L For "E" Generation

TEP075DG-S2D

Trenton Refrigeration TEP extended profile s- a2l for "e" generation evaporator.

31 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
fan qty3 countp.42
3 countp.49
3 countp.46
capacity65000 btu_hp.42
63100 btu_hp.42
61300 btu_hp.42
56400 btu_hp.42
52100 btu_hp.42
airflow11000 cfmp.42
5190 l_sp.42
refrigerant charge12 lbp.42
5.5 kgp.42
awef rating4.15 ratiop.47
suction od0.875 inchesp.49
distributor inlet0.875 inchesp.49
reverse cycle 3 pipe defrost side port connection od sweat0.5p.49
hot gas connection0.625 inchesp.49
distributor nozzleG2-1/2 part_idp.50
nozle hgG2-1/2p.50
motor hp0.5 hpp.46
motor fla12.6 ampsp.46
total watts1050 wattsp.46
1240 wattsp.46
mca15 ampsp.46
6.7 ampsp.46
fan motors standard ec motors mop a20p.46
total amps5.4 ampsp.46
drain pan heaters 208 230 1 60 mop a15p.46
voltage208 Vp.?
phase1 php.?
frequency60 Hzp.?

Sources: TEP_1109296 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
TEP075DG-S2D208-230/1/60Check availability

Nomenclature

Position / meaningValue
capacity code75
defrostG
fan count0
generation suffixD
temp classD
voltageS2

Cross references

BrandEquivalent modelBasis
KeepRiteKEP075DG-S2Dshared catalog stem
BallyBEP075DG-S2Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP075DG-S2D?

TEP075DG-S2D has a rated capacity of 65000 btu_h. See the specifications table for rating conditions.

What voltage does TEP075DG-S2D require?

TEP075DG-S2D runs on 208 V supply power.

Related models in TEP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.