Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
capacity67600 btu_hTEP + TEP-GEN-E p.4
66900 btu_hTEP + TEP-GEN-E p.4
66200 btu_hTEP + TEP-GEN-E p.4
55000 btu_hTEP + TEP-GEN-E p.4
54500 btu_hTEP + TEP-GEN-E p.4
53900 btu_hTEP + TEP-GEN-E p.4
67600 btu_hTEP + TEP-GEN-E p.4
66900 btu_hTEP + TEP-GEN-E p.4
66200 btu_hTEP + TEP-GEN-E p.4
airflow7000 cfmTEP + TEP-GEN-E p.4
3300 l_sTEP + TEP-GEN-E p.4
refrigerant charge12.4 lbTEP + TEP-GEN-E p.4
5.6 kgTEP + TEP-GEN-E p.4
11.7 lbTEP + TEP-GEN-E p.4
5.3 kgTEP + TEP-GEN-E p.4
11.2 lbTEP + TEP-GEN-E p.4
5.1 kgTEP + TEP-GEN-E p.4
11.9 lbTEP + TEP-GEN-E p.4
5.4 kgTEP + TEP-GEN-E p.4
awef rating9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.33
suction od1 3/8 inchesTEP + TEP-GEN-E p.37
distributor inlet1 1/8 inchessources differTEP p.37
1 1/8 inchessources differTEP-GEN-E p.35
0.875 inchessources differTEP-GEN-E p.36
1 1/8 inchesp.37
side port connection0.625 inchesp.37
0.625 inchesp.36
hot gas connection0.875 inchesp.37
shipping weight350 lbTEP + TEP-GEN-E p.38
159 kgTEP + TEP-GEN-E p.38
fan qty2 countTEP + TEP-GEN-E p.9
motor hp0.5 hpp.9
motor fla8.4 ampsp.9
total watts700 wattssources differTEP p.9
8837 wattssources differTEP p.9
mca15 ampssources differTEP p.9
29.3 ampssources differTEP p.9
29.2 ampssources differTEP p.12
mop20 ampsp.9
total amps23.4 ampsp.9
defrost heaters 208 230 3 60 mop a30p.9
esp circuit 208 230 3 60 mop a30p.12
voltage 208 230 1 60208-230/3/60p.62
1 x evaporator defrost kit dfk 10DFK-14p.62
1 x evaporator fuse package fp 105FP-113p.62
2 x evaporator defrost kit dfk 12DFK-23p.62
2 x evaporator fuse package fp 118FP-124p.62
voltage208 VTEP + TEP-GEN-E p.?
phase3 phTEP + TEP-GEN-E p.?
frequency60 HzTEP + TEP-GEN-E p.?
r454a erte 5 cEBSTE-11-Cp.40
r454c r455a r407a r448a r449a erve 5 cEBSVE-11-Cp.40
r404a r507 erse 3 1 2 c erse 4 cEBSSE-10-Cp.40
liquid line od9.5 mmp.51
suction line od34.9 mmp.51
maximum line length 3m minimum room area m214p.51
maximum line length 7 6m17p.51
maximum line length 15 2m21p.51
maximum line length 30 5m29p.51

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP_1109296, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP-GEN-E_1112932, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TEP068ME-T3D208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code068
capacity mbh68
defrostE
generation suffixD
temp classM
voltageT3

Parts

7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleE6order as E6S140--Check availability
Electronic expansion valveE3V55order as E3V55BWRC1--Check availability
Safety check valveCSOV17order as CSOV-17S--Check availability
Safety shutoff solenoidSSOV10--Check availability
Solenoid valveB10order as B10S2-5/8--Check availability
TXVEBSSE-10-C--Check availability
TXVEBSVE-11-C--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKEP068ME-T3Dshared catalog stem
BallyBEP068ME-T3Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP068ME-T3D?

TEP068ME-T3D has a rated capacity of 67600 btu_h. See the specifications table for rating conditions.

What voltage does TEP068ME-T3D require?

TEP068ME-T3D runs on 208 V supply power.

Related models in TEP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.