TEP065VE-T3D
Trenton Refrigeration TEP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 3 count | TEP + TEP-GEN-E p.6 ✓ | |
| capacity | 68500 btu_h | evap temp f: 0; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ |
| 66500 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 64600 btu_h | evap temp f: 20; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 59400 btu_h | evap temp f: 30; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 54900 btu_h | evap temp f: 40; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 55700 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.6 | |
| 54100 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| 52500 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.6 | |
| 48300 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.6 ✓ | |
| 44600 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.6 | |
| 68500 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 66500 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 64600 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 59400 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 54900 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 55700 btu_h | evap temp f: 0; refrigerant: R404A | p.8 | |
| 54100 btu_h | evap temp f: 10; refrigerant: R404A | p.8 | |
| 52500 btu_h | evap temp f: 20; refrigerant: R404A | p.8 | |
| 48300 btu_h | evap temp f: 30; refrigerant: R404A | p.8 | |
| 44600 btu_h | evap temp f: 40; refrigerant: R404A | p.8 | |
| airflow | 11000 cfm | TEP + TEP-GEN-E p.6 ✓ | |
| 5190 l_s | TEP + TEP-GEN-E p.6 ✓ | ||
| refrigerant charge | 13.7 lb | refrigerant: R407A/R407C | TEP + TEP-GEN-E p.6 ✓ |
| 6.2 kg | refrigerant: R407A/R407C | TEP + TEP-GEN-E p.6 ✓ | |
| 12.7 lb | refrigerant: R404A/R507 | p.6 | |
| 5.8 kg | refrigerant: R404A/R507 | p.6 | |
| 12.3 lb | refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 5.6 kg | refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 13.2 lb | refrigerant: R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 6 kg | refrigerant: R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 12.7 lb | refrigerant: R404A | p.8 | |
| 5.8 kg | refrigerant: R404A | p.8 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.35 ✓ |
| 4.15 ratio | refrigerant: R407A/R407C | p.35 | |
| 4.15 ratio | refrigerant: R448A/R449A | p.35 | |
| 4.15 ratio | refrigerant: R454A | p.35 | |
| 4.15 ratio | refrigerant: R454C | p.35 | |
| 4.15 ratio | refrigerant: R455A | p.35 | |
| 4.15 ratio | p.33 | ||
| suction od | 2 1/8 inches | TEP + TEP-GEN-E p.37 ✓ | |
| distributor inlet | 1 1/8 inches | defrost piping: reverse_cycle_3_pipe | p.37 |
| 1 3/8 inchessources differ | TEP p.37 | ||
| 1 1/8 inchessources differ | TEP-GEN-E p.36 | ||
| 1 3/8 inchessources differ | TEP-GEN-E p.37 | ||
| side port connection | 1 1/8 inches | defrost piping: reverse_cycle_3_pipe | p.37 |
| 1 1/8 inches | p.36 | ||
| hot gas connection | 1 1/8 inches | p.37 | |
| shipping weight | 450 lb | TEP + TEP-GEN-E p.38 ✓ | |
| 204 kg | TEP + TEP-GEN-E p.38 ✓ | ||
| motor hp | 0.5 hp | p.9 ✓ | |
| motor fla | 12.6 amps | p.9 | |
| total watts | 1050 wattssources differ | TEP p.9 | |
| 12940 wattssources differ | TEP p.9 | ||
| mca | 15 ampssources differ | TEP p.9 | |
| 42.8 ampssources differ | TEP p.9 | ||
| 42.7 ampssources differ | TEP p.12 | ||
| mop | 20 amps | p.9 | |
| total amps | 34.2 amps | p.9 | |
| defrost heaters 208 230 3 60 mop a | 45 | p.9 | |
| esp circuit 208 230 3 60 mop a | 45 | p.12 | |
| voltage 208 230 1 60 | 208-230/3/60 | p.63 | |
| 1 x evaporator defrost kit dfk 10 | DFK-16 | p.63 | |
| 1 x evaporator fuse package fp 105 | FP-024 | p.63 | |
| 2 x evaporator defrost kit dfk 12 | DFK-28 | p.63 | |
| 2 x evaporator fuse package fp 118 | FP-016 | p.63 | |
| voltage | 208 V | TEP + TEP-GEN-E p.? ✓ | |
| phase | 3 ph | TEP + TEP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TEP + TEP-GEN-E p.? ✓ | |
| r454a erte 5 zp ebste 8 zp | EBSTE-15-ZP | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.41 |
| r454c r455a r407a r448a r449a erve 5 zp ebsve 8 zp | EBSVE-15-ZP | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.41 |
| r404a r507 ebsse 6 zp | EBSSE-13-ZP | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.41 |
| liquid line od | 15.9 mm | p.51 | |
| suction line od | 41.3 mm | p.51 | |
| maximum line length 3m minimum room area m2 | 17 | p.51 | |
| maximum line length 7 6m | 22 | p.51 | |
| maximum line length 15 2m | 29 | p.51 | |
| maximum line length 30 5m | 44 | p.51 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TEP065VE-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 065 |
| capacity mbh | 65 |
| defrost | E |
| generation suffix | D |
| temp class | V |
| voltage | T3 |
Parts
13 factory parts for this unit: 13from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | C12✓ | Distributor nozzle; Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V55order as E3V55BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV17order as CSOV-17S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B14order as B14S2-5/8ODF✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | EBSSE-10-ZP✓ | evap temp f: -10 | - | - | Check availability |
| TXV | EBSSE-13-ZP✓ | evap temp f: -20; Thermostatic expansion valve (TXV) — evap temp f: -30 | - | - | Check availability |
| TXV | EBSSE-7-1/2-C✓ | evap temp f: 0 | - | - | Check availability |
| TXV | EBSVE-11-ZPorder as EBSVE-11-ZP40✓ | evap temp f: -10, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | EBSVE-15-ZPorder as EBSVE-15-ZP40✓ | evap temp f: -20, refrigerant: R407A/R448A/R449A; Thermostatic expansion valve (TXV) — evap temp f: -30, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | EBSVE-20-ZPorder as EBSVE-20-ZP40✓ | evap temp f: -40, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | EBSVE-8-C✓ | evap temp f: 0, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | OSE-21-ZP✓ | evap temp f: -40 | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KEP065VE-T3D | shared catalog stem ✓ |
| Bally | BEP065VE-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TEP065VE-T3D?
TEP065VE-T3D has a rated capacity of 68500 btu_h. See the specifications table for rating conditions.
What voltage does TEP065VE-T3D require?
TEP065VE-T3D runs on 208 V supply power.
Related models in TEP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.