TEP055HA-S2E
Trenton Refrigeration TEP evaporator.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 2 count | p.9 | |
| capacity | 54700 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.3 |
| 54200 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.3 | |
| 53600 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| 54700 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 54200 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 53600 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 44400 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.7 | |
| 44000 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.7 | |
| 43500 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.7 | |
| airflow | 7800 cfm | p.3 | |
| 3680 l_s | p.3 | ||
| refrigerant charge | 7.3 lb | refrigerant: R454A/R454C/R455A | p.3 |
| 3.3 kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 8 lb | refrigerant: R407A/R407C | p.5 | |
| 3.6 kg | refrigerant: R407A/R407C | p.5 | |
| 7.6 lb | refrigerant: R404A/R507 | p.7 | |
| 3.4 kg | refrigerant: R404A/R507 | p.7 | |
| 7.7 lb | refrigerant: R448A/R449A | p.5 | |
| 3.5 kg | refrigerant: R448A/R449A | p.5 | |
| awef rating | 9 ratio | p.33 | |
| suction od | 1 1/8 inches | p.35 | |
| distributor inlet | 0.875 inches | p.35 | |
| r454a erte 5 c | ERTE-8-C | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.40 |
| r454c r455a r407a r448a r449a erve 5 c | ERVE-8-C | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.40 |
| r404a r507 erse 3 1 2 c erse 4 c | ERSE-6-C | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.40 |
| liquid line od | 12.7 mm | p.51 | |
| suction line od | 28.6 mm | p.51 | |
| maximum line length 3m minimum room area m2 | 10 | p.51 | |
| maximum line length 7 6m | 12 | p.51 | |
| maximum line length 15 2m | 16 | p.51 | |
| maximum line length 30 5m | 24 | p.51 | |
| shipping weight | 290 lb | p.38 | |
| 132 kg | p.38 | ||
| motor hp | 1 hp | p.9 | |
| motor fla | 8.4 amps | p.9 | |
| motor watts | 700 watts | p.9 | |
| mca | 16 amps | p.9 | |
| mop | 20 amps | p.9 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TEP055HA-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 055 |
| capacity mbh | 55 |
| defrost | A |
| generation suffix | E |
| temp class | H |
| voltage | S2 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KEP055HA-S2E | shared catalog stem ✓ |
| Bally | BEP055HA-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TEP055HA-S2E?
TEP055HA-S2E has a rated capacity of 54700 btu_h. See the specifications table for rating conditions.
What voltage does TEP055HA-S2E require?
TEP055HA-S2E runs on 208 V supply power.
Related models in TEP