TEP051VE-S2E
Trenton Refrigeration TEP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 2 count | TEP + TEP-GEN-E p.6 ✓ | |
| capacity | 54200 btu_h | evap temp f: 0; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ |
| 52600 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 51100 btu_h | evap temp f: 20; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 47000 btu_h | evap temp f: 30; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 43400 btu_h | evap temp f: 40; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 44000 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.6 | |
| 42700 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| 41500 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.6 | |
| 38200 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.6 ✓ | |
| 35300 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.6 | |
| 54200 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 52600 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 51100 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 47000 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 43400 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 44000 btu_h | evap temp f: 0; refrigerant: R404A | p.8 | |
| 42700 btu_h | evap temp f: 10; refrigerant: R404A | p.8 | |
| 41500 btu_h | evap temp f: 20; refrigerant: R404A | p.8 | |
| 38200 btu_h | evap temp f: 30; refrigerant: R404A | p.8 | |
| 35300 btu_h | evap temp f: 40; refrigerant: R404A | p.8 | |
| airflow | 6900 cfm | TEP + TEP-GEN-E p.6 ✓ | |
| 3260 l_s | TEP + TEP-GEN-E p.6 ✓ | ||
| refrigerant charge | 12.4 lb | refrigerant: R407A/R407C | TEP + TEP-GEN-E p.6 ✓ |
| 5.6 kg | refrigerant: R407A/R407C | TEP + TEP-GEN-E p.6 ✓ | |
| 11.5 lb | refrigerant: R404A/R507 | p.6 | |
| 5.2 kg | refrigerant: R404A/R507 | p.6 | |
| 11.2 lb | refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 5.1 kg | refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.6 ✓ | |
| 11.9 lb | refrigerant: R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 5.4 kg | refrigerant: R448A/R449A | TEP + TEP-GEN-E p.6 ✓ | |
| 11.5 lb | refrigerant: R404A | p.8 | |
| 5.2 kg | refrigerant: R404A | p.8 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.35 ✓ |
| 4.15 ratio | refrigerant: R407A/R407C | p.35 | |
| 4.15 ratio | refrigerant: R448A/R449A | p.35 | |
| 4.15 ratio | refrigerant: R454A | p.35 | |
| 4.15 ratio | refrigerant: R454C | p.35 | |
| 4.15 ratio | refrigerant: R455A | p.35 | |
| 4.15 ratio | p.33 | ||
| suction od | 2 1/8 inches | TEP + TEP-GEN-E p.37 ✓ | |
| distributor inlet | 1 3/8 inches | defrost piping: reverse_cycle_3_pipe | p.37 |
| 1 3/8 inchessources differ | TEP p.37 | ||
| 1 3/8 inchessources differ | TEP-GEN-E p.36 | ||
| 0.875 inchessources differ | TEP-GEN-E p.36 | ||
| side port connection | 0.875 inches | defrost piping: reverse_cycle_3_pipe | p.37 |
| 0.875 inches | p.36 | ||
| hot gas connection | 0.875 inches | p.37 | |
| shipping weight | 340 lb | TEP + TEP-GEN-E p.38 ✓ | |
| 154 kg | TEP + TEP-GEN-E p.38 ✓ | ||
| mca | 48 ampssources differ | TEP p.12 | |
| NA ampssources differ | TEP p.12 | ||
| 16 ampssources differ | TEP-GEN-E p.11 | ||
| 48 ampssources differ | TEP-GEN-E p.11 | ||
| NA ampssources differ | TEP-GEN-E p.11 | ||
| esp circuit 1 208 230 1 60 mop a | 50 | p.12 | |
| esp circuit 2 208 230 1 60 mop a | NA | p.12 | |
| voltage | 208 V | TEP + TEP-GEN-E p.? ✓ | |
| phase | 1 ph | TEP + TEP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TEP + TEP-GEN-E p.? ✓ | |
| r454a erte 5 zp ebste 8 zp | EBSTE-11-ZP | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.41 |
| r454c r455a r407a r448a r449a erve 5 zp ebsve 8 zp | EBSVE-11-ZP | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.41 |
| r404a r507 ebsse 6 zp | EBSSE-10-ZP | refrigerant: R404A/R407A/R448A/R449A/R454A/R454C/R455A/R507 | p.41 |
| liquid line od | 9.5 mm | p.51 | |
| suction line od | 34.9 mm | p.51 | |
| maximum line length 3m minimum room area m2 | 16 | p.51 | |
| maximum line length 7 6m | 20 | p.51 | |
| maximum line length 15 2m | 28 | p.51 | |
| maximum line length 30 5m | 43 | p.51 | |
| motor hp | 0.5 hp | p.11 | |
| motor fla | 8.4 amps | p.11 | |
| motor watts | 700 watts | p.11 | |
| mop | 20 amps | p.11 | |
| total watts | 8837 wattssources differ | TEP-GEN-E p.11 | |
| NA wattssources differ | TEP-GEN-E p.11 | ||
| total amps | 38.4 ampssources differ | TEP-GEN-E p.11 | |
| NA ampssources differ | TEP-GEN-E p.11 | ||
| defrost heaters 208 230 1 60 circuit 1 mop a | 50 | p.11 | |
| defrost heaters 208 230 1 60 circuit 2 mop a | NA | p.11 | |
| esp circuit 1 208 230 1 60 mop a 30 50 | 50 | p.17 | |
| esp circuit mca | NA amps | circuit: 2 | p.17 |
| esp circuit 2 208 230 1 60 mop a na | NA | p.17 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TEP051VE-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 051 |
| capacity mbh | 51 |
| defrost | E |
| generation suffix | E |
| temp class | V |
| voltage | S2 |
Parts
12 factory parts for this unit: 12from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | C8✓ | Distributor nozzle; Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V45order as E3V45BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV17order as CSOV-17S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV10✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B10order as B10S2-5/8✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | EBSSE-10-ZP✓ | evap temp f: -20; Thermostatic expansion valve (TXV) — evap temp f: -30 | - | - | Check availability |
| TXV | EBSSE-13-ZP✓ | evap temp f: -40 | - | - | Check availability |
| TXV | EBSSE-7-1/2-C✓ | evap temp f: 0 | - | - | Check availability |
| TXV | EBSSE-7-1/2-ZPorder as EBSSE-7-1/2-ZP40✓ | evap temp f: -10 | - | - | Check availability |
| TXV | EBSVE-11-ZPorder as EBSVE-11-ZP40✓ | evap temp f: -10, refrigerant: R407A/R448A/R449A; Thermostatic expansion valve (TXV) — evap temp f: -20, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | EBSVE-15-ZPorder as EBSVE-15-ZP40✓ | evap temp f: -30, refrigerant: R407A/R448A/R449A; Thermostatic expansion valve (TXV) — evap temp f: -40, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | EBSVE-8-C✓ | evap temp f: 0, refrigerant: R407A/R448A/R449A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KEP051VE-S2E | shared catalog stem ✓ |
| Bally | BEP051VE-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TEP051VE-S2E?
TEP051VE-S2E has a rated capacity of 54200 btu_h. See the specifications table for rating conditions.
What voltage does TEP051VE-S2E require?
TEP051VE-S2E runs on 208 V supply power.
Related models in TEP