TEP051ME-T4E

Trenton Refrigeration TEP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty2 countTEP + TEP-GEN-E p.4
capacity51200 btu_hTEP + TEP-GEN-E p.4
50700 btu_hTEP + TEP-GEN-E p.4
50200 btu_hTEP + TEP-GEN-E p.4
41600 btu_hTEP + TEP-GEN-E p.4
41200 btu_hTEP + TEP-GEN-E p.4
40800 btu_hTEP + TEP-GEN-E p.4
51200 btu_hTEP + TEP-GEN-E p.4
50700 btu_hTEP + TEP-GEN-E p.4
50200 btu_hTEP + TEP-GEN-E p.4
airflow7900 cfmTEP + TEP-GEN-E p.4
3730 l_sTEP + TEP-GEN-E p.4
refrigerant charge8 lbTEP + TEP-GEN-E p.4
3.6 kgTEP + TEP-GEN-E p.4
7.6 lbTEP + TEP-GEN-E p.4
3.4 kgTEP + TEP-GEN-E p.4
7.2 lbTEP + TEP-GEN-E p.4
3.3 kgTEP + TEP-GEN-E p.4
7.7 lbTEP + TEP-GEN-E p.4
3.5 kgTEP + TEP-GEN-E p.4
awef rating9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.35
9 ratiop.33
suction od1 1/8 inchesTEP + TEP-GEN-E p.37
distributor inlet0.875 inchesTEP + TEP-GEN-E p.37
0.875 inchesp.37
side port connection0.5 inchesp.37
0.5 inchesp.36
hot gas connection0.875 inchesp.37
shipping weight315 lbTEP + TEP-GEN-E p.38
143 kgTEP + TEP-GEN-E p.38
mca14.6 ampssources differTEP p.13
16 ampssources differTEP-GEN-E p.14
14.6 ampssources differTEP-GEN-E p.14
esp circuit 460 3 60 mop a15TEP + TEP-GEN-E p.13
voltage460 VTEP + TEP-GEN-E p.?
phase3 phTEP + TEP-GEN-E p.?
frequency60 HzTEP + TEP-GEN-E p.?
r454a erte 5 cERTE-8-Cp.40
r454c r455a r407a r448a r449a erve 5 cERVE-8-Cp.40
r404a r507 erse 3 1 2 c erse 4 cEBSSE-6-Cp.40
liquid line od9.5 mmp.51
suction line od28.6 mmp.51
maximum line length 3m minimum room area m210p.51
maximum line length 7 6m12p.51
maximum line length 15 2m16p.51
maximum line length 30 5m24p.51
motor hp1 hpp.14
motor fla5 ampsp.14
motor watts700 wattsp.14
mop20 ampsp.14
total watts8837 wattsp.14
total amps11.7 ampsp.14
defrost heaters 460 3 60 mop a15p.14
esp circuit mca14.6 ampsp.18

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP_1109296, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TEP-GEN-E_1112932, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TEP051ME-T4E460/3/60Check availability

Nomenclature

Position / meaningValue
capacity code051
capacity mbh51
defrostE
generation suffixE
temp classM
voltageT4

Parts

7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleG4--Check availability
Electronic expansion valveE3V45order as E3V45BWRC1--Check availability
Safety check valveCSOV13order as CSOV-13S--Check availability
Safety shutoff solenoidSSOV10--Check availability
Solenoid valveB9order as B9S2--Check availability
TXVEBSSE-6-C--Check availability
TXVERVE-8-C--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKEP051ME-T4Eshared catalog stem
BallyBEP051ME-T4Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP051ME-T4E?

TEP051ME-T4E has a rated capacity of 51200 btu_h. See the specifications table for rating conditions.

What voltage does TEP051ME-T4E require?

TEP051ME-T4E runs on 460 V supply power.

Related models in TEP