Trenton Refrigeration · TEP · Extended Profile Evaporators- A2L For "E" Generation
TEP051ME-T3D
Trenton Refrigeration TEP extended profile s- a2l for "e" generation evaporator.
68 extracted specifications, each traceable to its source document and page.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 2 count | p.4 | |
| 2 count | p.4 | ||
| 2 count | p.4 | ||
| 2 count | p.37 | ||
| 2 count | p.37 | ||
| 2 count | p.9 | ||
| capacity | 51200 btu_h | evap temp f: 25 | p.4 |
| 50700 btu_h | evap temp f: 15 | p.4 | |
| 50200 btu_h | evap temp f: 10 | p.4 | |
| 41600 btu_h | evap temp f: 25 | p.4 | |
| 41200 btu_h | evap temp f: 15 | p.4 | |
| 40800 btu_h | evap temp f: 10 | p.4 | |
| 51200 btu_h | evap temp f: 25 | p.4 | |
| 50700 btu_h | evap temp f: 15 | p.4 | |
| 50200 btu_h | evap temp f: 10 | p.4 | |
| airflow | 7900 cfm | p.4 | |
| 3730 l_s | p.4 | ||
| 7900 cfm | p.4 | ||
| 3730 l_s | p.4 | ||
| 7900 cfm | p.4 | ||
| 3730 l_s | p.4 | ||
| refrigerant charge | 8 lb | p.4 | |
| 3.6 kg | p.4 | ||
| 7.6 lb | p.4 | ||
| 3.4 kg | p.4 | ||
| 7.2 lb | p.4 | ||
| 3.3 kg | p.4 | ||
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.35 |
| 9 ratio | refrigerant: R407A/R407C | p.35 | |
| 9 ratio | refrigerant: R448A/R449A | p.35 | |
| 9 ratio | refrigerant: R454A | p.35 | |
| 9 ratio | refrigerant: R454C | p.35 | |
| 9 ratio | refrigerant: R455A | p.35 | |
| suction od | 1 1/8 inches | p.37 | |
| 1 1/8 inches | p.37 | ||
| distributor inlet | 0.875 inches | p.37 | |
| 0.875 inches | p.37 | ||
| reverse cycle 3 pipe defrost side port connection od sweat | 0.5 | p.37 | |
| hot gas connection | 0.875 inches | p.37 | |
| txv model | EBSSE-6-C part_number | refrigerant: R404A/R507 | p.39 |
| ERVE-8-C part_number | refrigerant: R407A/R407C/R448A/R449A | p.39 | |
| distributor nozzle | G4 part_id | p.40 | |
| G4 part_id | p.41 | ||
| electronic expansion valve | E3V45 part_number | p.41 | |
| solenoid valve | B9 part_number | p.41 | |
| safety solenoid valve | SSOV10 part_number | p.41 | |
| safety check valve | CSOV13 part_number | p.41 | |
| shipping weight | 315 lb | p.38 | |
| 143 kg | p.38 | ||
| motor hp | 0.5 hp | p.9 | |
| motor fla | 8.4 amps | p.9 | |
| total watts | 700 watts | p.9 | |
| 8837 watts | p.9 | ||
| mca | 15 amps | p.9 | |
| 29.3 amps | p.9 | ||
| 29.2 amps | p.12 | ||
| fan motors standard ec motors mop a | 20 | p.9 | |
| total amps | 23.4 amps | p.9 | |
| defrost heaters 208 230 3 60 mop a | 30 | p.9 | |
| esp circuit 208 230 3 60 mop a | 30 | p.12 | |
| voltage 208 230 1 60 | 208-230/3/60 | p.62 | |
| 1 x evaporator defrost kit dfk 10 | DFK-14 | p.62 | |
| 1 x evaporator fuse package fp 105 | FP-113 | p.62 | |
| 2 x evaporator defrost kit dfk 12 | DFK-23 | p.62 | |
| 2 x evaporator fuse package fp 118 | FP-124 | p.62 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: TEP_1109296 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TEP051ME-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 51 |
| defrost | E |
| fan count | 0 |
| generation suffix | D |
| temp class | M |
| voltage | T3 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KEP051ME-T3D | shared catalog stem ✓ |
| Bally | BEP051ME-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TEP051ME-T3D?
TEP051ME-T3D has a rated capacity of 51200 btu_h. See the specifications table for rating conditions.
What voltage does TEP051ME-T3D require?
TEP051ME-T3D runs on 208 V supply power.
Related models in TEP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.