Trenton Refrigeration · TEP · Extended Profile Evaporators- A2L For "E" Generation

TEP051CG-S4D

Trenton Refrigeration TEP extended profile s- a2l for "e" generation evaporator.

33 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
fan qty2 countp.42
2 countp.49
2 countp.49
2 countp.46
capacity41600 btu_hp.42
41200 btu_hp.42
40800 btu_hp.42
airflow7900 cfmp.42
3730 l_sp.42
refrigerant charge6.6 lbp.42
3 kgp.42
awef rating9 ratiop.47
suction od0.625 inchesp.49
0.625 inchesp.49
distributor inlet0.625 inchesp.49
0.5 inchesp.49
medium temperature air and electric defrost models liquid line od sweat0.375p.49
reverse cycle 3 pipe defrost side port connection od sweat0.5p.49
hot gas connection0.5 inchesp.49
distributor nozzleJ3/4 part_idp.50
nozle hgJ3/4p.50
motor hp1 hpp.46
motor fla5 ampsp.46
total watts700 wattsp.46
887 wattsp.46
mca15 ampsp.46
2.4 ampsp.46
fan motors standard ec motors mop a20p.46
total amps1.9 ampsp.46
drain pan heaters 208 230 1 60 mop a15p.46
voltage460 Vp.?
phase1 php.?
frequency60 Hzp.?

Sources: TEP_1109296 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
TEP051CG-S4D460/1/60Check availability

Nomenclature

Position / meaningValue
capacity code51
defrostG
fan count0
generation suffixD
temp classC
voltageS4

Cross references

BrandEquivalent modelBasis
KeepRiteKEP051CG-S4Dshared catalog stem
BallyBEP051CG-S4Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TEP051CG-S4D?

TEP051CG-S4D has a rated capacity of 41600 btu_h. See the specifications table for rating conditions.

What voltage does TEP051CG-S4D require?

TEP051CG-S4D runs on 460 V supply power.

Related models in TEP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.